FXMQ-MA | Daikin
Sound pressure level
Cooling
At low fan speed
dBA
45
45
At high fan speed
dBA
48
48
Standard Accessories
Installation and operation manual
Installation and operation manual
Installation and operation manual
Connection pipes
Connection pipes
Connection pipes
Sealing pads
Sealing pads
Sealing pads
Clamps
Clamps
Clamps
Screws
Screws
Screws
Refrigerant
Type
R-410A
R-410A
Power input – 50Hz
Cooling
At high fan speed
kW
1.294
1.465
Heating
At high fan speed
kW
1.294
1.465
Cooling capacity
Total capacity
At high fan speed
kW
22.4 (1)
28.0 (1)
Piping connections
Liquid
OD
mm
9.52
9.52
Type
Flare connection
Flare connection
Gas
OD
mm
19.1
22.2
Type
Braze connection
Braze connection
Drain
PS1B
PS1B
Dimensions
Unit
Width
mm
1,380
1,380
Depth
mm
1,100
1,100
Height
mm
470
470
Casing
Material
Galvanised steel plate
Galvanised steel plate
Weight
Unit
kg
137
137
Fan
External static pressure – 50Hz
High
Pa
221 (4)
270 (4)
External static pressure – 60Hz
High
Pa
270
270
Air flow rate – 50Hz
Cooling
At high fan speed
m³/min
58
72
At low fan speed
m³/min
50
62
Air flow rate – 60Hz
Cooling
High
m³/min
58
72
Low
m³/min
50
62
Heating capacity
Total capacity
At high fan speed
kW
25.0 (2)
31.5 (2)
Current – 50Hz
Maximum fuse amps (MFA)
A
15
15
Power supply
Phase
1~
1~
Name
VE
VE
Frequency
Hz
50/60
50/60
Voltage
V
220-240/220
220-240/220
Notes
(1) – Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
(1) – Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
(2) – Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
(2) – Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
(3) – Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
(3) – Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
(4) – The external static pressure is changeable: change the connectors inside the electrical box, this pressure means: High static pressure – Standard
(4) – The external static pressure is changeable: change the connectors inside the electrical box, this pressure means: High static pressure – Standard
(5) – Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% and more.
(5) – Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% and more.
(6) – Sound pressure levels are measured at 220V.
(6) – Sound pressure levels are measured at 220V.
(7) – Reference acoustic pressure 0 dB = 20 Pa.
(7) – Reference acoustic pressure 0 dB = 20 Pa.
(8) – Sound values are measured in an anechoic room.
(8) – Sound values are measured in an anechoic room.
(9) – Operation sound differs with operation and ambient conditions
(9) – Operation sound differs with operation and ambient conditions
(10) – Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(10) – Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
(11) – Maximum allowable voltage range variation between phases is 2%.
(11) – Maximum allowable voltage range variation between phases is 2%.
(12) – MCA/MFA: MCA = 1.25 x FLA
(12) – MCA/MFA: MCA = 1.25 x FLA
(13) – MFA ≤ 4 x FLA
(13) – MFA ≤ 4 x FLA
(14) – Next lower standard fuse rating minimum 15A
(14) – Next lower standard fuse rating minimum 15A
(15) – Select wire size based on the value of MCA
(15) – Select wire size based on the value of MCA
(16) – Instead of a fuse, use a circuit breaker
(16) – Instead of a fuse, use a circuit breaker